AEQ3500W – Square-Outlet Horizontal Standard Total-Heat Fresh Air System
The 3500 CBM/h entry model of the AEQ-W horizontal total-heat series. The horizontal cabinet is arranged for plant rooms and roof frames, with rectangular duct connections at both ends and side access for core and filter servicing. Total-heat recovery, three operating points and 380V three-phase supply make it suitable for offices, restaurants and retail floors.
Technical Specifications
| Model | Rated voltage (V/Hz) | Air volume H / M / L (CBM/h) | Static pressure H / M / L (Pa) | Power H / M / L (W) | Temp. efficiency H / M / L Summer/Winter (%) | Enthalpy efficiency H / M / L Summer/Winter (%) | Noise H / M / L [dB(A)] | Reference weight (kg) |
|---|---|---|---|---|---|---|---|---|
| AEQ3500W | 380V/50Hz | 2500 / 3000 / 3500 | 300 / 250 / 100 | 1950 / 2100 / 2200 | 76 / 75 / 72 | 59/68 / 58/68 / 54/65 | 54 / 58 / 61 | 272 |
| AEQ4000W | 380V/50Hz | 2500 / 3000 / 4000 | 370 / 350 / 250 | 2510 / 2580 / 2650 | 76 / 75 / 74 | 59/68 / 59/67 / 58/66 | 58 / 60 / 62 | 297 |
| AEQ5000W | 380V/50Hz | 3000 / 4000 / 5000 | 400 / 320 / 250 | 3062 / 3405 / 3900 | 77 / 76 / 75 | 60/68 / 59/66 / 58/65 | 61 / 63 / 65 | 382 |
| AEQ7000W | 380V/50Hz | 5000 / 6000 / 7000 | 280 / 250 / 160 | 3491 / 3990 / 4380 | 76 / 75 / 73 | 60/66 / 59/64 / 57/61 | 62 / 64 / 66 | 495 |
| AEQ8000W | 380V/50Hz | 6000 / 7000 / 8000 | 320 / 280 / 250 | 4275 / 4750 / 5130 | 76 / 75 / 74 | 58/66 / 55/64 / 53/63 | 65 / 67 / 68 | 603 |